How to Fix Continuous Filter Alarm on Geospring Water Heater

GE GeoSpring water heater error codes

GE

These error code explanations can help you diagnose a problem with your GE GeoSpring water heater.

The control panel beeps and the error code appears in the digital display when the control detects a component failure. For example, when the control detects that the evaporator fan isn't running, the GeoSpring water heater displays the F4 code and its control panel beeps. Follow the troubleshooting tips shown in the chart below to diagnose and repair the F4 code or other codes that appear in the display.

To find repair parts, search for your model number to find a complete list of replacement parts for your water heater.

For repair how-to help, visit the PartsDirect repair help section, which includes repair help for water heaters, major appliances, lawn and garden equipment, garage door openers, vacuum cleaners and more.

Error Code

Condition

DIY advice

FA

Compressor discharge temperature not rising

Check/Repair

The T4 sensor (compressor outlet temperature sensor) must detect at least a 20-degree temperature rise during the first 30 minutes of run time. Disconnect the power or unplug the water heater and check T4 sensor mounting, wiring and ohm resistance. T4 sensor should measure approximately 55k ohms at 77 degrees Fahrenheit or 188k-2k when the compressor discharge temperature is 30-250 degrees. If all the steps above check out and the compressor outlet temperature still is not rising, call a service technician to check the sealed refrigerant system for proper charge and to check the thermal expansion valve (TXV).

Possible parts

T4 sensor, Thermal expansion valve

FB

Compressor discharge temperature not stable

Check/Repair

The T4 sensor (compressor outlet temperature) must be greater than 120 degrees Fahrenheit after 30 minutes of run time. Disconnect power or unplug the water heater and check T4 sensor mounting, wiring and ohm resistance. T4 sensor should measure approximately 55k ohms at 77 degrees or 188k-2k when the compressor discharge temperature is 30-250 degrees. If all the steps above check out and the compressor discharge temperature still is not stable, call a service technician to check the sealed refrigerant system for proper charge and the thermal expansion valve (TXV) operation.

Possible parts

T4 sensor, Thermal expansion valve

FC

Evaporator frosted over

Check/Repair

The T3a sensor (evaporator inlet temperature) must be greater than 20 degrees Fahrenheit after 30 minutes of run time. Disconnect power or unplug the water heater and check T3a sensor mounting, wiring and ohm resistance. The T3 sensor should measure approximately 10k ohms at 77 degrees or 57k-3k when the evaporator inlet temperature is 15-130 degrees. If all the steps above check out, call a service technician to check the sealed refrigerant system for proper charge and the thermal expansion valve (TXV) operation.

Possible parts

T3a sensor, Thermal expansion valve

FD

Super heat is too low

Check/Repair

Disconnect power or unplug the water heater and then check temperature sensors T3a, T3b and T5 mounting, wiring and the ohm resistance of each sensor. Sensors T3a, T3b and T5 should measure approximately 10k ohms at 77 degrees Fahrenheit. Check and clean the filter. If all the above steps check out, call a service technician to check the sealed refrigerant system for proper charge and the thermal expansion valve (TXV) operation.

Possible parts

T3a sensor, T3b sensor, T5 sensor, Thermal expansion valve

FE

Discharge temperature above the limit

Check/Repair

The compressor discharge temperature exceeded 240 degrees Fahrenheit. Verify that T4 sensor (compressor outlet temperature sensor) measures approximately 188k-2k ohms after 30 minutes of run time. Disconnect power or unplug the water heater and then check T4 sensor mounting, wiring and ohm resistance. If all the above steps check out, call a service technician to check the sealed refrigerant system for proper charge and the thermal expansion valve (TXV) operation.

Possible parts

T4 sensor, Thermal expansion valve

F2

Tank temperature sensor failure

Check/Repair

The control checks the T2 tank sensor temperature before the compressor starts and it must be 30-u2013170 degrees Fahrenheit. Disconnect power or unplug the water heater and then check T2 sensor mounting, wiring and ohm resistance. The ohm resistance should measure approximately 10k ohms at 77 degrees. If the T2 sensor is okay, replace the power control board (PCB).

Possible parts

T2 sensor, Power control board

F3

Compressor failure

Check/Repair

The control energized the compressor but the current sensor does not detect any current flow. Disconnect power or unplug the water heater and then check the compressor, relay and wiring. Call a service technician if the compressor has failed.

F4

Fan failure

Check/Repair

Disconnect power or unplug the water heater and then check the evaporator for a loose or broken wire connection. If fan motor wiring connections are okay, replace the evaporator fan motor. If the F4 code returns after replacing the evaporator fan, replace the power control board (PCB).

Possible parts

Fan motor, Power control board

F5

T3a sensor failure

Check/Repair

Before the compressor starts, the control checks that T3a, T3b and T5 sensors are all within 15 degrees Fahrenheit of each other. Disconnect power or unplug the water heater and then check T3a sensor mounting, wiring and resistance. The ohm resistance of the T3a, T3b and T5 sensors should measure approximately 10k ohms at 77 degrees. If the sensors are okay, replace the power control board (PCB).

Possible parts

T3a sensor, T3b sensor, T5 sensor, Power control board

F6

T3b sensor failure

Check/Repair

Disconnect power or unplug the water heater and then check the T3b (evaporator sensor) sensor mounting, wiring and the ohm resistance of the sensors. The ohm resistance of sensors T3a, T3b and T5 must measure approximately 10k ohms at 77 degrees Fahrenheit. If the sensors are okay, replace the power control board (PCB).

Possible parts

T3b sensor, T3a sensor, T5 sensor, Power control board

F7

T4 sensor failure

Check/Repair

Disconnect power or unplug the water heater and then check the T4 (compressor outlet sensor) mounting, wiring and ohm resistance of the T4 sensor. The ohm resistance of T4 sensor should measure approximately 55k ohms at 77 degrees Fahrenheit. If the sensor is okay, replace the power control board (PCB).

Possible parts

T4 sensor, Power control board

F8

T5 sensor failure

Check/Repair

Disconnect power or unplug the water heater and then check the T5 (ambient temperature sensor) mounting, wiring and ohm resistance. The ohm resistance should measure approximately 10k ohms at 77 degrees Fahrenheit. If the sensor is okay, replace the power control board (PCB).

Possible parts

T5 sensor, Power control board

F9

Lower heating element failure

Check/Repair

Disconnect power or unplug the water heater and then check the lower heating element and wiring. Check the wiring and connections on the power control board (PCB) and lower heating element. Disconnect the wires from the lower heating element and measure the heating element for ohm resistance using a multimeter. The heating element should measures 12.8-18.75 ohms of resistance. If the lower element and wiring is okay, replace the power control board.

How-to help

Possible parts

Lower heating element, Power control board

F10

Upper heating element failure

Check/Repair

Disconnect power or unplug the water heater and then check the upper heating element and wiring. Check the wiring and connections on the power control board (PCB). Disconnect and measure the heating element for ohm resistance using a multimeter. The heating element should measure 12.8-18.75 ohms of resistance. If the upper element and wiring are okay, replace the power control board.

How-to help

Possible parts

Upper heating element, Power control board

Symptoms common to all water heaters

Choose a symptom to see related water heater repairs.

Articles and videos common to all water heaters

Use the advice and tips in these articles and videos to get the most out of your water heater.